Maximum Line-Set Distance Formula
a. Measured rise x 1.7= Calculated
Rise 35 ft. Max) [10.66 meters]
b. Measured drop x 6.6= Calculated
Drop 15 ft. Max) [4.57 meters]
c. Measured Horizontal Distance = actual measurement.
d. Total Calculated Distance (A+B+C)=Total
Calculated Distance (100 ft. Max.) [30.48 meters]
EXAMPLES:
a. Insert measured rise (R) into the formula and multiply
it by 1.7 to get a calculated rise.
example: A condenser located 15 ft. [4.572 meters]
above the ice machine has a 25.5 ft. [8.874 meters]
calculated total (15 ft. x 1.7 = 25.5).
b. Insert measured drop (D) into formula and multiply by
6.6 to get a calculated drop.
example: A condenser located 8 ft. [2.438 meters]
below the ice machine has a 52.8 ft. [16.093 meters]
calculated total (8 ft. x 6.6 = 52.8 ft.).
c. Insert measured horizontal distance into formula. No
calculation is necessary. (6 ft.) [1.828 meters].
d. Add the calculated rise, calculated drop, and hori-
zontal distance together to get the total calculated
distance (25.5 + 52.8 + 6) equals 84.3 ft. [25.694 me-
ters]. If 100 ft. [30.48 meters] total calculated dis-
tance is exceeded, the condenser must be moved to
a new location which permits proper equipment op-
eration.
Caution
If a line-set rise is followed by a line-set drop, a second
line-set rise cannot be made.
Or
If a line-set drop is followed by a line-set rise, a second
line-set drop cannot be made.
3. Lengthening or Reducing the Line-Set Lengths
In most cases, by routing the line-set properly, shortening
H
R
D
H
R
H
D
AIR
FLOW
AIR
FLOW
AIR
FLOW
COMBINATION OF
DROP(S)
WITH HORIZONTAL
COMBINATION OF RISE AND
DROP(S)WITH HORIZONTAL