Remote Condenser Location
1. Physical Line-Set Length: 55 Ft. Maximum [16.764 me-
ters]
The ice machine compressor must have the proper oil re-
turn. Line-set rises, drop, or horizontal runs greater than the
maximum distance allowed will exceed the compressor start-
up and pumping design limits, and will result in poor oil re-
turn to the compressor.
Line-Set Rise: 35 Ft. Maximum [10.66 meters]
Line-Set Drop: 15 Ft. Maximum [4.57 meters]
2. Calculated Line-Set Distance: 100 Ft. [30.48 meters]
To prevent the combination of rises, drops and horizontal
runs exceeding the compressor start-up and pumping design
limit, the following calculations should be made:
A - (RISE) CONDENSER HIGHER THAN EVAP.
MAX. 35 FT.
B - LINE LENGTH 15 FT.: EXAMPLE
B - LINE LENGTH 35 FT.: EXAMPLE
C - (DROP) CONDENSER LOWER THAN EVAP. 15 FT.: MAX.
A
B
B
C
NOTE: MAX. LINE-SET
LENGTH FOR IMI CORNELIUS
FLAKERS IS 55 FT.
DO NOT CONFUSE LINE
LENGTH WITH CALCULATED
LINE DISTANCE.