TP00952
November 26, 2001 17
LED INDICATORS
The LEDs are board circuit indicators. If the LED in the functional board circuit is complete, check compo-
nent.
Example: Contactor does not energize and LED is “ON”, board circuit is OK. Check contactor, coil, leads,
& connections.
Yellow:
S Evaporator switch(s) (proximity)
S Delay (located on the electrical box front).
Green:
S Water dump valve
S Compressor contactor
S Water Pump
S Hot Gas Valve
S Condenser Fan (cycles on & off with fan)
S Fill Valve
Red:
S Error (located on the electrical box front).
S Ice thickness Adjustment.
Refer to flash codes for control and system diagnostics. Add the flash codes before status indicators
(See Figure 11).
Error LED
Delay LED
Red
Yellow
FIGURE 11
FLASHING CODE FOR SELF DIAGNOSTICS
Delay LED “Yellow” Error LED “Red”
1 High condenser Temperature Delay 1 High Condenser Temp. Shut Down
2 Water Fill Time Out Delay 2 Water Fill Time Out Shut Down
3 Failed Harvest Delay 3 Failed Harvest Shut Down
4 Maximum Freeze Time Out Delay 4 Maximum Freeze Time Out Shut Down
6 Low Condenser Temperature Delay 6 Low Condenser Temperature Shut Down
7 Open Thermistor Shut Down
8 End of Clean Cycle Shut Down
STATUS INDICATOR
Green LED Condenser Fan
Yellow LED Left Water Curtain
Green LED Hot Gas Valve
Green LED Water Pump
Yellow LED Right Water Curtain
Green LED Compressor Contactor
Red LED Error
Green LED Dump Valve
Green LED Fill Valve
Yellow LED Delay
Red LED Ice Thickness Adjustment