GENERAL DESCRIPTION
This section gives the Unit description, theory of operation, and design data.
IMPORTANT: To the user of this manual – This manual is a guide for installing, operating, and main-
taining this equipment. Refer to the Table of Contents for page location for detailed information per-
taining to questions that arise during installation, operation, service, or maintenance of this equip-
ment.
NAMING CONVENTION CH–1502–A
CH – Denotes “CH” series chiller product.
15 – Denotes 18,000 BTU/Hr. Nominal capacity. “1.5 TON”.
02 – Voltage 230/3/60,
OD – 230/1/60
03 – 460/3/60
A – Denotes Air-Cooled Condenser
W – Denotes Water Cooled Condenser
The CH-1502-A model chiller from Remcor is designed to provide a continuous flow of clean cooling water at a
constant temperature.
The unit incorporates a refrigeration system with all necessary operating controls and safety devices. The hous-
ing is constructed of painted cold rolled steel panels, angles and a galvanized base with optional casters. All
flow requirements must be externally provided as there is no pump or tank provided with the CH-1502-A.
The chiller is designed to operate in a clean industrial or laboratory environment where ambient temperatures
range from 40 - 110_F. For applications which reject dirt or particles to the cooling fluid (i.e. EDM’s) it is neces-
sary to filter the fluid before it enters the chiller (#20 mesh strainer, not supplied with unit). Fluid contaminated
with metal particles or dirt can clog the evaporator causing a decrease in capacity. There is an air filter installed
to keep the condenser fins clean. A dirty condenser leads to a decrease in capacity and higher than normal re-
frigerant pressure.
WARNING: Allow unit to sit in ambient for 24 hours before starting out of box. Never
operate the chiller with panels removed. Verify that air flow is unobstructed.
Table 1. SPECIFICATION
Cooling Capacity @ 70_F Ambient: 18,000 BTU/Hr.
Compressor: Copeland Corporation CRA1-0150-TF5
1-1/2 Horsepower
Power Requirements: 230 Volts - 60 Hz, 7.3 Amps, 3 Phase
Condenser:
Total Heat Rejection to room
Air Cooled,
25,000 BTU/Hr.
Refrigerant: HCFC–22 6.0 Lbs.
Temperature Control:
Set Point Range:
Temperature probe type:
Probe location:
Differential:
Eliwell digital display
40 – 100_F
Thermistor
Water inlet
$ 1_F
Dimensions: 20”L x 20”W x 25”H
Water Connections: 3/4” FPT stainless steel couplings