Xtreme Ice Training Manual
TP00952
October 17, 2005 25
SAFETY (NEW SOFTWARE)
NOTE: After S/N 63K0344BC050 for self–contained units and S/N 63M0351BC056 for remote units.
SAFETY FEATURES
1. Failed Freeze Shutdown
2. Failed Harvest Shutdown
3. Bin Full Delay
4. Low Condenser Temperature Warning
5. High Condenser Temperature Warning and Shutdown
6. Open Condenser Thermistor Shutdown
7. Inlet Warning
8. Failed Water System Shutdown
9. Failed Water Temperature Shutdown
10. Open Water Thermistor Shutdown
FLASHING CODE FOR SELF DIAGNOSTICS (300’S, 500’S, 600’S,
800’S, 1000’S, AND 1200’S)
NOTE: After S/N 63K0344BC050 for self–contained units and S/N 63M0351BC056 for remote units.
Warning LED Error LED
1 High Condenser Temperature Warning 1 High Condenser Temp. Shutdown
2 Failed Freeze Time Out Shutdown
3 Failed Harvest Shutdown
4 Low Condenser Temperature Warning
5 Water Inlet Warning 5 Failed Water System Shutdown
6 End of Clean Cycle Shutdown
8 Open Condenser Thermistor Shutdown
FLASHING CODE FOR SELF DIAGNOSTICS (1400’S AND 1800’S)
NOTE: After S/N 63K0344BC050 for self–contained units and S/N 63M0351BC056 for remote units.
Warning LED Error LED
1 High Condenser Temperature Warning 1 High Condenser Temp. Shutdown
2 Failed Freeze Time Out Shutdown
3 Failed Harvest Shutdown
4 Low Condenser Temperature Warning 4 Failed Water Temperature Shutdown
5 Water Inlet Warning 5 Failed Water System Shutdown
6 End of Clean Cycle Shutdown
7 Open Water Thermistor Shutdown
8 Open Condenser Thermistor Shutdown