Trouble Probable Cause Remedy
COMPRESSOR OPERATES
CONTINUOUSLY BUT DOES
NOT FORM SUFFICIENT ICE
BANK.
A. Cooling capacity is exceeded
by over-drawing.
A. Reduce amount of drinks drawn
per given time.
B. Unit located in excessively hot
area or air circulation through
condenser coil is restricted.
B. Relocate unit or check and if
necessary, clean condenser coil
as instructed.
NOTE: Ice bank freezes from bottom of evaporator upward. A
refrigerant leak or insufficient charge might show an ice bank at
bottom and not at top of evaporator.
AGITATOR MOTOR NOT
OPERATING.
A. Power switch (if applicable) in
OFF position.
A. Place power switch in
ON position.
B. Unit power cord or
refrigeration assembly power
cord unplugged.
B. Connect power cord(s).
C. No power source (blown fuse
or tripped circuit breaker).
C. Replace fuse or reset circuit
breaker. (NOTE: Fuse or circuit
breaker are not part of Unit).
D. Agitator motor propeller
obstructed.
D. Remove obstruction.
E. Low voltage. E. Voltage must be at least 103 volts
(115 VAC unit) or 208 (230 VAC
unit) at compressor terminals
when compressor is trying to
start.
F. Loose, disconnected, or
broken wiring.
F. Tighten connections or replace
broken wiring.
G. Inoperative agitator motor. G. Replace agitator motor.