Installation Guide
Model 230
Wet/Wet Dierential Pressure Transducer
1-800-257-3872 Toll Free
1-978-264-0292 Fax
www.setra.com Web Site
Vista de pagina 0
1 2 3 4 5 6 ... 11 12

Indice de contenidos

Pagina 1 - Installation Guide

1Installation GuideModel 230Wet/Wet Dierential Pressure Transducer1-800-257-3872 Toll Free1-978-264-0292 Faxwww.setra.com Web Site

Pagina 2 - Table of Contents

106.0 LIMITED WARRANTY AND LIMITATION OF LIABILITYSETRA warrants its products to be free from defects in materials and workmanship, subject to the fol

Pagina 3 - Setra Model 230

11SS2010 Rev. J 4/4/14

Pagina 5 - 1/4” NPT

21.0 GENERAL INFORMATION ... 32.0 MECHANICAL INSALLATIONS ... 3 2.1 Media Compatib

Pagina 6

3Setra Model 230Wet/Wet Dierential Pressure Transducer1.0 GENERAL INFORMATION Every Model 230 has been tested and calibrated before shipment. Setra

Pagina 7 - 3.0 ELECTRICAL INSTALLATION

42.6 Installation Procedures If the Model 230 is supplied with an optional 3-valve or 5 valve manifold assembly, refer to Section 2.8 and 2.9. Option

Pagina 8 - 4.0 CALIBRATION

52.8 Optional 3-Valve Manifold ProcedureThe 3-Valve Manifold Assembly is normally shipped with valves V1 and V2 closed and V3 open.To place the Model

Pagina 9 - Calibration Services

62.9 Optional 5-Valve Assembly ProcedureThe 5-Valve Manifold Assembly is normally shipped with valves V1, V2, V4, and V5 closed, and V3 open.To Place

Pagina 10 - SS2010 Rev. J 4/4/14

73.0 ELECTRICAL INSTALLATION To access electrical connections remove cover on top of the Model 230 For CE compliance a shielded cable with both ends

Pagina 11

84.0 CALIBRATION The 230 transducer is factory calibrated and should require no eld adjustment. Whenever possible, any zero and/or span osets shoul

Pagina 12

94.3 Current Output Zero Adjustment While monitoring the current output, and with both pressure ports open to atmosphere, the zero may be adjusted. F